System Sensor CO1224T Installation And Maintenance Instructions

This product is intended for use in ordinary indoor locations.

General Description

• Listed to UL standard 2075

• 4 wire, system monitored

• Local sounder

• Low current draw

• Alarm relay, Form C

• Trouble relay, Form A

• Test/Hush button

• SEMS wiring terminals

• Mount to single gang electrical box or surface mount to wall

or ceiling

• Optional drywall anchors included

Figure 1. Alarm Location Diagram:

CARBON MONOXIDE ALARM

LOCATION FOR MULTI-LEVEL RESIDENCE

40 mA (75 mA test)

30 VDC @ 0.5 A

30 VDC @ 0.5 A

85 dBA min. in alarm (at 10ft)

Physical Specifications

Operating Temperature Range:

Operating Humidity Range:

Wire Gauge Acceptance:

Table 1. Detector Operation Modes:

*Temp 4 pattern is repeated pattern of four short indications fol-

lowed by a five second pause.

When the detector has been in alarm for 30 minutes the alarm

signal will be given once every minute.

If ambient conditions return to normal, the detector will self-re-

store out of alarm and into Normal (standby) mode.

Hush feature: If required, the audible alarm can be silenced for

5 minutes by pushing the button marked "Test/Hush". The red

alarm light will continue to flash in temp-4 pattern. If carbon

monoxide is still present after the 5 minute hush period, the au-

dible alarm will sound. The hush facility will not operate at levels

above 350 ppm (parts per million) carbon monoxide.

Trouble feature: When the sensor supervision is in a trouble con-

dition (such as a sensor that has been tampered with), the detec-

tor will send a trouble signal to the panel. The detector must then

be replaced.

End of Life Timer feature: When the detector has reached the

end of its life, the trouble contact will open. This indicates that

the CO sensor inside the detector has passed the end of its life

and must be replaced. This detector's lifespan is approximately

six years from the date of manufacture. Refer to Detector Replace-

ment on page 3.

Per UL 2075, it is mandatory that a trouble signal be sent to the

panel upon CO cell trouble or cell end of life. Refer to Figure 4

for wiring of the trouble relay.

3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

0° to 40°C (32° to 104°F)

per minute

I56-3111-000

Related Manuals for System Sensor CO1224T

Carbon monoxide detector (2 pages)

Carbon monoxide detector with realtest technology (2 pages)

Carbon monoxide detector with realtest (2 pages)

Carbon monoxide detector (4 pages)

Selectable output wall chime/strobes for fire protective signaling systems (4 pages)

Selectable output wall chime/strobes for fire protective signaling systems (4 pages)

Pluciin detector base (2 pages)

Vane-type waterflow detectors (4 pages)

Led indoor selectable-output horn strobes and strobes (11 pages)

Projected beam type smoke detector (13 pages)

Vane-type waterflow detectors (42 pages)

Ds2475 series spectralert dual strobe (2 pages)

Direct wire ionization smoke detectors (4 pages)

Summary of Contents for System Sensor CO1224T